- New
Safer than solenoid testers and fully compliant with NFPA 70E, (when used properly per Article 110.4 Use of Equipment (A) Test Instruments and Equipment), the T+Pro helps electricians and technicians work safer by indicating the presence of voltage, even when the batteries are dead. Additional functionality, such as a GFCI trip, easy to read LCD screen, resistance measurement up to 9.99 kΩ, and a built-in flashlight make the T+Pro the first voltage tester that electricians reach for.
The Fluke T+Pro Electrical Tester indicated AC/DC voltage in three different ways:
(edit with the Customer Reassurance module)
(edit with the Customer Reassurance module)
(edit with the Customer Reassurance module)
Temperature
Operating: -10°C to 55°C (14°F to 131°F)
Storage: -30°C to 60°C (-22°F to 140°F)
Relative Humidity
90%: 0°C to 30°C (32°F to 86°F)
75%: 30°C to 40°C (86°F to 104°F)
45%: 40°C to 50°C (104°F to 122°F)
Altitude
Operating: 2,000 m (approx. 6,561.6 ft)
Storage: 10,000 m (approx. 32,808.4 ft)
Battery Type/Life: AAA (2); 40 hours
Shock, Vibration: Sinusoidal vibration per MIL-PRF-28800F for a Class 2 instrument
Safety: ISA-82.02.01 (IEC 61010-1 Mod) Second Edition, CAN/CSA-C22.2 No. 61010-1 Second Edition, IEC 61010 - 1 to 1000 V CAT III/600 V CAT IV, Compliance to NFPA 70E1
AC Bandwidth: 45 Hz to 66 Hz
Maximum Working Voltage: 1000 V AC/DC
Maximum Measurable Voltage: 600 V AC/DC
Duty Cycle: Indefinitely for voltages up to 240 V
For voltages between 240 V and 600 V the duty cycle is 30 s on / 300 s off
For voltages above 240 V the tester must connect to a voltage source only for a MAXIMUM of 30 s and then disconnect for a MINIMUM of 300 s
Voltage Hazard LED: LEDs turn on at voltages > 30 V AC/DC ±35%
LED Voltage Indication Levels: 12 V, 24 V, 48 V, 120 V, 208 V, 240 V, 277 V, 480 V, 600 V
LEDs: LEDs turn on between 90% and 100% of the indicated voltage on the LED, except for the 12 V LED which turns on between 50% and 100%
LCD Accuracy
AC voltage: ±(3% rdg + 2 digits)
DC voltage: ±(2% rdg + 2 digits)
Resistance: ±(5% rdg + 3 digits)
LCD Resolution: 0.1 V for voltages < 50 V, 1 V for voltages ≥ 50 V
0.01 kΩ for resistance measurement
GFCI Test Current: 100 V - 150 V @ 6 mA - 9 mA AC, 150 V - 240 V < 12 mA
Standard Input Test Current: < 5 mA
Size (H x W x L) : 1.3 x 2.15 x 7.6 in (3.3 x 5.46 x 19.3 cm )
Weight: 9.9 oz (0.28 kg)